Your ultimate defence against corrosion. Follow our expert guidelines to ensure long-lasting protection for every surface.

Internal Mild Steel

Ensure surfaces are degreased and free of contamination using A925 – Metal degreaser (follow instructions as per data sheet). Ensure all Corroless data sheet preparation procedures are strictly followed such as spread rates, abrasive blasting, power tool cleaning and water jet standards etc. Apply 1st coat within 4 hours of abrasive blasting. Practical coverage is project dependent. Ensure surfaces are free from preparation debris and are clean and dry. All data sheets can be found at the back of this manual.

Internal/Dry Exposure

Preparation: Corroded steel power wire brushed to a bright
surface to St 2 AS 1627.2. Alkyd Single pack system

1st Coat
Apply Corroless S1 or S2 at 80 µ WFT (35 µ DFT)
2nd and 3rd coat
Apply Corroless RF 15 at 120 µ WFT (60 µ DFT ) tinted to approved colour
TDF = 155 microns minimum
Internal/Wet Exposure

Preparation: Abrasive Blasting Sa 2½ of AS 1627.4. Two pack system

1st Coat
Apply Corroless E at 90 µ WFT( 50 µ DFT)
2nd and 3rd coat
Apply Corroless RF 60 at 50 µ WFT ( 30 DFT)
TDF = 110 microns minimum
Internal/PH/ Chemicals/
Humidity

Preparation: Abrasive Blasting Sa 2½ of AS 1627.4.
Two pack system

1st Coat
Apply Corroless EP at 210 µ WFT( 200 µ DFT)
2nd and 3rd coat

Apply Corroless RF 35 at 210 µ WFT ( 200 DFT)

TDF = 600 microns minimum
Specification subject to NZS/AS 1627; Preparation of surfaces NZS/AS 2312 Protection of mild steel; AS 3894 Determination of Dry Film thickness